H261--Triennial Electrical System Inspection and Maintenance
Active
Contract Opportunity
Notice ID
36C25023Q0050
Related Notice
Department/Ind. Agency
VETERANS AFFAIRS, DEPARTMENT OF
Sub-tier
VETERANS AFFAIRS, DEPARTMENT OF
Office
250-NETWORK CONTRACT OFFICE 10 (36C250)
Looking for contract opportunity help?

Procurement Technical Assistance Centers (PTACs) are an official government contracting resource for small businesses. Find your local PTAC (opens in new window) for free government expertise related to contract opportunities.

General Information View Changes
  • Contract Opportunity Type: Combined Synopsis/Solicitation (Updated)
  • All Dates/Times are: (UTC-04:00) EASTERN STANDARD TIME, NEW YORK, USA
  • Updated Published Date: Oct 17, 2022 03:43 pm EDT
  • Original Published Date: Oct 05, 2022 03:22 pm EDT
  • Updated Date Offers Due: Oct 19, 2022 04:00 pm EDT
  • Original Date Offers Due: Oct 19, 2022 04:00 pm EDT
  • Inactive Policy: Manual
  • Updated Inactive Date: Dec 18, 2022
  • Original Inactive Date: Dec 18, 2022
  • Initiative:
    • None
Classification
  • Original Set Aside: Service-Disabled Veteran-Owned Small Business (SDVOSB) Set-Aside (FAR 19.14)
  • Product Service Code: H261 - EQUIPMENT AND MATERIALS TESTING- ELECTRIC WIRE AND POWER DISTRIBUTION EQUIPMENT
  • NAICS Code:
    • 238210 - Electrical Contractors and Other Wiring Installation Contractors
  • Place of Performance:
    Chalmers P. Wyllie VA Ambulatory Center Columbus , OH 43219
Description View Changes
The purpose of this solicitation amendment is to provide answers to vendor questions. Please see below.
On the walkthrough, it was identified that the responsibility of coordinating any service disconnect via the utility falls on the awarded contractor. Considering contractor s normally don t handle service disconnection for an the end-user, will you please provide the process for how this will need to be executed? Additionally, will you please identify any costs (if any) for service disconnection since this will be taking place off normal business hours, or on Fri/Sat? A onetime initial utility disconnect and reconnect must be coordinated with AEP and paid by the contractor. VA will approve this service. Â After the initial disconnect and reconnect for preventive maintenance (PM) on the Digitrip and Disconnect Gear at the main feed, VA Engineering staff can perform shut downs without any charge to the contractor.

Please confirm whether or not 480v single phase power will be provided for primary injection testing. 480V, 1Ø will be provided for primary injection testing.

Transformer of 500KVA or larger shall be cleaned interiorly, inspected for sign of overheating with an infrared thermal detecting equipment and inspected for any damages to the housing, connection points, or insulation.
THIS IS ONLY REQUESTING CLEANING AND INFRARED OF TRANSFORMERS NO TESTING? - SEE ATTACHMENT #2, All testing will follow ANSI/NETA MTS-2019 SECTION 7.0 THRU 8.0
Dry type transformers must be thoroughly cleaned, both interior and exterior, and inspected for overheating with infrared thermal detecting equipment.
THIS IS ONLY REQUESTING CLEANING AND INFRARED OF TRANSFORMERS NO TESTING? - SEE ATTACHMENT #2, All testing will follow ANSI/NETA MTS-2019 SECTION 7.0 THRU 8.0
Electrical equipment (including, but not limited to Automatic Transfer Switches (ATS) switchgears, switchboards, distribution panels, motor control centers, and all related components) are required to be inspected, tested, maintained, and/or calibrated as follows:
INSPECTED, TESTED, MAINTAINED, AND/OR CALIBRATED AS FOLLOWS BUT NO TESTING IS SPELLED OUT BELOW BESIDES GROUND FAULT DEVICES? - SEE ATTACHMENT #2, All testing will follow ANSI/NETA MTS-2019 SECTION 7.0 THRU 8.0
Calibrate and maintain adjustable protective relays.
HOW MANY AND WHAT TYPE ARE THEY? - 1- MV main Eaton relay energy center MV Schweitzer relays all others 480 volt and under are square-d and Eaton/ cutter-hammer. As well this is covered under attachment #2, also please see equipment list document in original solicitation.
Full testing shall be performed for all breakers rated above 200 Amps throughout the facility.
FULL TESTING WOULD ASSUME PRIMARY INJECTION TESTING ON DRAW OUT BREAKERS AND SECONDARY INJECTION TESTING OF BOLT IN BREAKERS AS A VA STANDARD? MEDIUM VOLTAGE BREAKERS, SWITCHES, ATS UNITS HAVE NO DEFINED TESTING STANDARD. INFRARED AND CLEANING WOULD BE ASSUMED UNDER THIS SCOPE? DIGITAL RELAYS WOULD NOT BE PART OF THIS SCOPE. WE RECOMMEND INJECTING VOLTAGE/CURRENT AND OPERATING OUTPUTS AS A MINIMUM FOR MICROPROCESSOR BASED RELAYS - SEE ATTACHMENT #2 All testing will follow ANSI/NETA MTS-2019 SECTION 7.0 THRU 8.0 All breakers 400 amp and above will be primary injection weather bolt in or draw out type.

Mary Jane Crim
Contracting Officer
maryjane.crim@va.gov
Attachments/Links
Contact Information
Contracting Office Address
  • VISN 10 CONSOLIDATED CONTRACTING 4100 WEST 3RD STREET
  • DAYTON , OH 45428
  • USA
Primary Point of Contact
Secondary Point of Contact


History

TRY FOR FREE

Not a USAOPPS Member Yet?

Get unlimited access to thousands of active local, state and federal government bids and awards in All 50 States.

Start Free Trial Today >